Cable Fill Calculator

Standard
Metric

Tray Type

Open Bottom Power greater than 2000V NEC 392.22(A) - Sum of the diameters of all cables shall not exceed the cable tray width.
Single Conductor - 1\0 to 4\0 NEC 392.22(B)(1)(d) - Sum of the diameters of all cables shall not exceed the cable tray width.
Single Conductor - 250 to 1000 kcmil NEC 392.22(B)(1)(b) - Sum of the cross-sectional areas of all cables shall not exceed Column 2 of Table 392.22(B)(1).
Single Conductor - larger than 1000 kcmil NEC 392.22(B)(1)(b) - NEC 392.22(1)(a) - Sum of the diameters of all cables shall not exceed the cable tray width.
Multi Conductor - 4\0 or larger NEC 392.22(A)(1)(a) - Sum of the diameters of all cables shall not exceed the cable tray width.
Multi Conductor - smaller than 4\0 NEC 392.22(A)(1)(b) - Sum of the cross-sectional areas of all cables shall not exceed Column 1 of Table 392.22(A)(1)
Control and Signal or Data NEC 392.22(A)(2) - Sum of the cross-sectional areas of all cables shall not exceed 50% of the cross-sectional area of the tray.
Solid Bottom Power greater than 2000V NEC 392.12 - Sum of the diameters of all cables shall not exceed the cable tray width.
Single Conductor - 1\0 to 4\0 Not permitted
Single Conductor - 250 to 1000 kcmil Not permitted
Single Conductor - larger than 1000 kcmil Not permitted
Multi Conductor - 4\0 or larger NEC 392.22(A)(3)(a) - Sum of the diameters of all cables shall not exceed the cable tray width.
Multi Conductor - smaller than 4\0 NEC 392.22(A)(3)(b) - Sum of the cross-sectional areas of all cables shall not exceed Column 3 of Table 392.22(A)(1)
Control and Signal or Data NEC 392.22(A)(4) - Sum of the cross-sectional areas of all cables shall not exceed 40% of the cross-sectional area of the tray.
Cable ID Cable Type Choose Cable QTY OD (mm) Weight (kg/m)